Property 01

Address

City, State

Currently this building is unoccupied. Ten rooftop HVAC units are in need of replacement(2, 3, 5, 6, 8, 18, 19, 22, 32 & 33), the remaining units are all newer and in good condition. Units 20, 25, 27 & 30 are in need of repairs.

Projectd Actual Status Description
Proposal Date 2/14/2015 2/16/2015    
Approval Date 2/28/2015 2/28/2015    
Permits Filed 3/1/2015 3/1/2015    
Permits Aproval 5 - 7 days 3/5/2015    
Start Date 3/8/2015 3/8/2015 On time  
Completion Date 4/21/2015 4/18/2015 Completed Early All went as planned
Inspection Date 4/21/2015 4/18/2015 Passed Electric

Existing Equipment

System # Unit # Type Brand Model # Serial # Cooling Heating Fan Belts Air Filters Year Condition Voltage Fuses
02 02 RTU-A/C Carrier 50CD006600 1283G64 593 5 Ton 14 kw E Belts Filters Year Poor 460/3ph 3 FRS-R-30
03 03 RTU-A/C Carrier 50CD006600 0783G62 75 5 Ton 14 kw E Belts Filters Year Poor 460/3ph 3 FRS-R-30
05 05 RTU-A/C Carrier 50CD006600 5282G5 882 5 Ton 14 kw E Belts Filters Year Poor 460/3ph 3 FRS-R-30
06 06 RTU-A/C Carrier 50CD006600 1283G4 592 5 Ton 14 kw E Belts Filters Year Poor 460/3ph 3 FRS-R-30
08 08 RTU-A/C Carrier 50CD006600 1283G64 595 5 Ton 14 kw E Belts Filters Year Poor 460/3ph 3 FRS-R-30
09 09 RTU-A/C Carrier 50TM-006-A-601-- 1507G10355 5 Ton 14 kw E Belts Filters Year Good 460/3ph 3 FRS-R-30
10 10 RTU-A/C Carrier 50TM-006-A-601-- 4306G40217 5 Ton 14 kw E Belts Filters Year Good 460/3ph 3 FRS-R-30
12 12 RTU-A/C Carrier 50TM-006-A-601-- 4406G40154 5 Ton 14 kw E Belts Filters Year Good 460/3ph 3 FRS-R-30
18 18 RTU-A/C Carrier 50CD006600 5282G5 8825 5 Ton 14 kw E Belts Filters Year Poor 460/3ph 3 FRS-R-30
19 19 RTU-A/C Carrier 50CD006600 0483G62 189 5 Ton 14 kw E Belts Filters Year Poor 460/3ph 3 FRS-R-30
20 20 RTU-A/C Carrier 50TM-006-A-601-- 0407G10287 5 Ton 14 kw E Belts Filters Year Good 460/3ph 3 FRS-R-30
22 22 RTU-A/C Carrier 50CD006600 5282G5 882 5 Ton 14 kw E Belts Filters Year Poor 460/3ph 3 FRS-R-30
23 23 Condenser York H1CE150A25C NCGM084047 5 Ton 14 kw E Belts Filters Year Good 208/230/3ph 3 FRS-R-70
24 HP Split Trane TSC036A3R0A1 6091011902L 3 Ton NA NA NA 2004 Good 200/230/1ph 2-20 Amp
24 AH Split Trane ? ? 3 Ton NA NA NA 2004 Good 200/230/1ph 2-20 Amp
25 25 RTU-A/C Carrier 50TM-006-A-601-- 5006G30050 5 Ton 14 kw E Belts Filters Year Needs Repair 460/3ph 3 FRS-R-30
26 26 RTU-A/C Carrier 50TM-006-A-601-- 5006G30049 5 Ton 14 kw E Belts Filters Year Good 460/3ph 3 FRS-R-30
27 27 RTU-A/C Carrier 50TM-006-A-601-- 4906G30280 5 Ton 14 kw E Belts Filters Year Needs Repair 460/3ph 3 FRS-R-30
29 29 RTU-A/C Carrier 50TM-006-A-601-- 5006G30047 5 Ton 14 kw E Belts Filters Year Needs Repair 460/3ph 3 FRS-R-30
30 30 RTU-A/C Carrier 50TM-006-A-601-- 0207G20210 5 Ton 14 kw E Belts Filters Year Needs Repair 460/3ph 3 FRS-R-30
31 31 RTU-A/C Carrier 50TM-006-A-601-- 1507G10354 5 Ton 14 kw E Belts Filters Year Good 460/3ph 3 FRS-R-30
32 32 RTU-A/C Carrier 50CD006600 1283G84 591 5 Ton 14 kw E Belts Filters Year Poor 460/3ph 3 FRS-R-30
33 33 RTU-A/C Carrier 50CD006600 1283G64 596 5 Ton 14 kw E Belts Filters Year Poor 460/3ph 3 FRS-R-30
35 HP Split Trane 2TWB0024A1000AB 4042ULE4F 2 Ton NA NA NA 2004 Good 200/230/1ph 2-20 Amp
35 AH Split Trane ? ? 2 Ton NA NA NA 2004 Good 200/230/1ph 2-20 Amp
45 HP Split Trane 2TWB0024A1000AB 4044UC44F 2 Ton NA NA NA 2004 Good 200/230/1ph 2-20 Amp
45 AH Split Trane ? ? 2 Ton NA NA NA 2004 Good 200/230/1ph 2-20 Amp
55 HP Split Trane 2TWB0024A1000AB 4044UC54F 2 Ton NA NA NA 2004 Good 200/230/1ph 2-20 Amp
55 AH Split Trane ? ? 2 Ton NA NA NA 2004 Good 200/230/1ph 2-20 Amp

Notes:

1/14/2015

Unit 02

This unit should be replaced, it is in poor condition. The condenser coil is damaged. The evaporator coil is in poor condition. The electric heat package does not operate. The economizer does not operate properly and the pre-screens need to be replaced.

Unit 03

This unit should be replaced, it is in poor condition. The condenser coil is damaged. The evaporator coil is in poor condition. The electric heat package does not operate. The economizer does not operate properly and the pre-screens need to be replaced.

Unit 05

This unit should be replaced, it is in poor condition. The condenser coil is damaged. The evaporator coil is in poor condition. The electric heat package does not operate. The economizer does not operate properly and the pre-screens need to be replaced.

Unit 06

This unit should be replaced, it is in poor condition. The condenser coil is damaged. The evaporator coil is in poor condition. The electric heat package does not operate. The economizer does not operate properly and the pre-screens need to be replaced.

Unit 08

This unit should be replaced, it is in poor condition. The condenser coil is damaged. The evaporator coil is in poor condition. The electric heat package does not operate; elements are shorted to ground. The economizer does not operate properly and the pre-screens need to be replaced.

Unit 09

This unit is in good condition but has no power to it.

Unit 10

This unit is in good condition and operates properly.

Unit 12

This unit is in good condition and operates properly.

Unit 18

This unit should be replaced, it is in poor condition. The condenser coil is damaged. The evaporator coil is in poor condition. The electric heat package does not operate; elements are shorted to ground. The economizer does not operate properly and the pre-screens need to be replaced.

Unit 19

This unit should be replaced, it is in poor condition. The condenser coil is damaged. The evaporator coil is in poor condition. The electric heat package does not operate; elements are shorted to ground. The economizer does not operate properly and the pre-screens need to be replaced.

Unit 20

This unit is in good condition but needs repairs. Low voltage wiring needs to be repaired and the blower wheel shaft and pulley need to be replaced.

Unit 22

This unit should be replaced, it is in poor condition. The condeser coil is damaged. The evaporator coil is in poor condition. Most parts have been removed.

Unit 23

This unit is in good condition and operates properly.

Unit 24

Unit 25

This unit is in good condition but needs repairs. Low voltage wiring needs to be repaired and the blower wheel shaft and pulley need to be replaced.

Unit 26

This unit is in good condition and operates properly.

Unit 27

This unit is in good condition but needs repairs. Low voltage wiring needs to be repaired and the blower wheel shaft and pulley need to be replaced.

Unit 29

This unit is in good condition but needs repairs. Low voltage wiring needs to be repaired and the blower wheel shaft and pulley need to be replaced.

Unit 30

This unit is in good condition but needs repairs. Low voltage wiring needs to be repaired and the blower wheel shaft and pulley need to be replaced.

Unit 31

This unit is in good condition and operates properly.

Unit 32

This unit should be replaced, it is in poor condition. The condenser coil is damaged. The evaporator coil is in poor condition. The electric heat package does not operate; elements are shorted to ground. The economizer does not operate properly and the pre-screens need to be replaced.

Unit 33

This unit should be replaced, it is in poor condition. The condenser coil is damaged. The evaporator coil is in poor condition. The electric heat package does not operate. The economizer does not operate properly and the pre-screens need to be replaced.

Unit 35

This unit is in good condition and operates properly.

Unit 45

This unit is in good condition and operates properly.

Unit 55

This unit is in good condition and operates properly.

View Photo Gallery »

.

Property 02

Address

City, State

Water has leaking through the roof into the dollar store and common area behind the dollar store. We are going to disconnect the unit and move it out of the way for Elite roofing to complete the roof repairs. After the repairs we will reinstall the unit with new duct work to existing drops.

Projectd Actual Status Description
Proposal Date 1/13/2015 1/13/2015    
Approval Date 1/13/2015      
Permits Filed NA NA    
Permits Aproval NA NA    
Start Date 1/20/2015      
Completion Date 1/23/2015      
Inspection Date        

Existing equipment

System # Unit # Type Brand Model # Serial # Cooling Heating Fan Belts Air Filters Year Condition Voltage Fuses
01 01 RTU Goodman CPG0601403DXXXBA 1008328772 5 Ton 140K BTUs gas Belts Filters 2008 fAIR 208/230/3ph 3

Notes:

1/20/2015

Removed RTU

Disconnected and moved the rooftop package unit on the lower roof for the roof repair. Should be re-installing the unit on Thursday the 22nd.

1/15/2015

Scheduled withElite Roofing

Received email from Paul Cooper that we are scheduled to disconnect the rooftop unit on 1/20/2015.

1/13/2015

Project Approval

Received approval by Tim Herb to disconnect the rooftop unit and reinstall it after the roof has been repaired. Tim Forwarded me the contact information for Paul Cooper from Elite Roofing to schedule the work.

1/13/2015

Project proposal

Provided proposal for the project, $1,500.00 to disconnect the rooftop unit then reinstall it with new duct work to existing drops.

1/06/2015

Request for project

Received a request to look for source of roof leak to see if it was from the HVAC rooftop unit. Also was asked to provide an estimate to disconnect the unit and then reinstall it after the roof repairs were made.

View Photo Gallery »